Cable voltage drop
Calculate the voltage drop of a single- or three-phase circuit and find the smallest cross-section within the limit.
Circuit and cable
Enter the load, line length and cable. The result updates as you type.
The model ignores cable reactance, which understates the result above about 50 mm² Cu (70 mm² Al). Conductivity is taken at about 20°C; at operating temperature the resistance is higher. Voltage drop is one sizing criterion: also check current-carrying capacity and shock protection. The result is for preliminary calculations and must be checked in the design and by measurement. It does not confirm that the installation complies with standards.
Method and assumptions
1f: ΔU% = 200 / U_f · I · R · cos φ
3f: ΔU% = √3 · 100 / U_N · I · R · cos φ
R = l / (γ · S)
I: load current from active power and cos φ; l: line length in metres; S: cross-section in mm²; γ: conductivity, 56 m/(Ω·mm²) for copper and 33 for aluminium. Source: Warsaw University of Technology, eSezam, “Voltage drop calculations”, formulas 4.3–4.8.