Switchgear and apparatus

Capacitor bank size for power factor correction

Calculate the capacitor bank needed to raise cos φ and see the power triangle before and after correction.

CalculatorVisualisationMethod: Qc = P·(tan φ₁ − tan φ₂)
01 / MEASUREMENT AND TARGET

Correction

Enter the active power, the present power factor and the target.

Often 0.93–0.95 (tan φ ≤ 0.4). The value comes from your supply contract.
POWER TRIANGLE
P = 200 kWQ before = 176 kvarQ after = 66 kvar
CAPACITOR BANK RATING
110.6 kvar
tan φ: 0.88 → 0.33
Apparent power before / after267 / 211 kVACurrent after correction79% of present
i

The result is the bank rating at a constant load. A varying load needs an automatic bank with steps, and distorted current needs a detuned bank with reactors. Base the choice on measurements over a longer period. The result is for preliminary calculations and must be checked in the design and by measurement. It does not confirm that the installation complies with standards.

Method and assumptions

Qc = P · (tan φ₁ − tan φ₂)

P: active power; φ₁, φ₂: phase angle before and after correction. Check example: 200 kW, cos φ 0.75, target tan φ = 0.2 gives about 136 kvar.