Transformers

Transformer rated and short-circuit current

From the rating, voltages and impedance voltage uk, calculate the rated currents and the short-circuit current at the LV terminals.

CalculatorVisualisationMethod: Ik = In·100/uk% (infinite upstream fault level)
01 / RATING

Transformer

Enter the nameplate data. The result is for a fault at the LV terminals.

Usually 4–6% for distribution transformers. Take it from the nameplate.
SHORT-CIRCUIT CURRENT AT LV TERMINALS
15.2 kA
16.7 × rated current
Rated current LV909 ARated current HV24.2 AShort-circuit power10.5 MVA
SHORT-CIRCUIT CURRENT FOR STANDARD RATINGS (uk = 6.0%)
2.4
100
3.8
160
6.0
250
9.6
400
15.2
630
19.2
800
24.1
1000
30.1
1250
38.5
1600
48.1
2000
60.1
2500
Ik [kA] by rating [kVA] · voltages and uk unchanged

Standard ratings

Rating [kVA]In HV [A]In LV [A]Ik LV [kA]
1003.81442.4
1606.22313.8
2509.63616.0
40015.45779.6
63024.290915.2
80030.81,15519.2
100038.51,44324.1
125048.11,80430.1
160061.62,30938.5
200077.02,88748.1
250096.23,60860.1
i

Symmetrical three-phase fault at the LV terminals with an infinite upstream fault level. The impedance of the HV network, cables and busbars lowers the real current; the voltage factor c from IEC 60909-0 raises it by 5–10%. Do a full short-circuit study before selecting switchgear. The result is for preliminary calculations and must be checked in the design and by measurement. It does not confirm that the installation complies with standards.

Method and assumptions

In = S / (√3 · U)
Ik = In · 100 / uk%

Check examples: 630 kVA, 400 V, uk 4% gives 909 A and 22.7 kA; 1000 kVA, 400 V, uk 6% gives 1443 A and 24.1 kA.